Axial Fans (General
Details):
Specifications
IMPELLERS
Impellers have
blades of true aerofoil section cast in aluminum silicon alloy,
accurately balanced for all speeds and possessing non-overloading
power characteristics.
CASING
A simple robust long
casing of welded construction with end flanges and stiffeners. The
casing carries an extra adjustable platform for the foot mounted
motor. Access doors in the side of the casing are provided as
standard for all AFX fans.
DRIVE
Type AFX fans are
indirect driven by an externally mounted motor through V ropes.
Double bearings are mounted in one piece cast iron housing supported
centrally in the fan casing by high tensile steel ties. The EN-8
shaft supports the impeller and the fan V pulley. Pulleys may be
changed for duty variations but we should always be consulted.
BEARINGS
Taper roller
bearings are used contained in a one piece bearing housing within
the fan casing. The bearings are grease packed and lubrication tubes
are carried to the outside of the housing.
Top

FINISH
Standard finish is
sprayed light gray enamel while the impeller is sprayed silver
aluminum paint.
AIR FLOW
Loading Direct chart
picture [Fig- 203/205/207]
The direction of airflow for standard
type AFX fans is Airflow A in accordance with the diagram. The
fans may be mounted horizontally or vertically in accordance with
the figures of construction.
OTHER AXIAL FAN TYPES
-
AXIAL FANS Most axial fans are manufactured by Multivent
-
[Axial
Fans Div.] under ICEBERG brand , a part of the
-
Multivent Engineers. The fans are normal industrial direct
-
driven
fans available with either long or medium length casing.
-
The fan
casing is painted with smoke grey after manufacture
-
and is
fitted with an access door. The impeller is cast in
-
aluminum silicon alloy with either six or ten blades of true
-
aerofoil
selection which can be set to any angle from 8o to
-
36o if
required. The driving motor is mounted centrally within
-
the
duct and the impeller supported on the motor shaft.
MINE VENTILATION FANS
The Multivent range
of axial fans includes those designed for
main, booster and auxiliary mines ventilation
incorporating the special features required
for this application.
GUIDE VANE FANS
Certain high duty
requirements may be met by the use of fans having stationery guide
vanes usually mounted immediately downstream from the impeller.
Top

TWO STAGE FANS
For high working
pressure beyond the reach of the normal single stage fans, we are
able to supply two stage axial fans. Construction and specification
are generally similar to that for the normal fans and incorporate
the same features and advantages but two impellers are mounted in
series on the drive shaft with a set of guide vanes after each
impeller. Two stage fans are available for direct motor drives or
for indirect driven fans.
CONTRA ROTATING FANS
Also for producing
high pressure in excess of the normal single stage fans,
two fans with impellers of opposite hand and rotation
may be bolted together in series to form a
contra-rotating unit. This is an extremely
flexible system since the output may be varied by idling
one stage as well as changing pulley ratios to effect
speed changes. Contra rotating fans are available for direct
motor drive or as indirect driven fans.
MARINE TYPE FANS
Fans can be provided with marine
features for arduous operations
under these conditions. Application include
the ventilation of engine and boiler rooms and
accommodation and cargo spaces. Outputs of the marine fans are
identical with the normal
industrial types and are of similar construction but
with extra features to suit the specification of
marine application. A marine direct
driven axial fan is also manufactured with
the swing out casing for accessibility to
the motor and impeller.
BIFURCATED FANS
The ICEBERG
range of bifurcated fans has been designed for
applications handling obnoxious fumes, dust-laden air and
gases at normal or high temperatures. This
range of fans is made in steel plate for
normal and high temperatures and also for the
highly corrosive fumes. This arrangement is
ideal for accessibility to the motor that is
open to atmosphere and works therefore
in the lower ambient temperature.
SILENCERS
A range of silencers is available for use with
axial fans.
AIR FLOW
The
direction for airflow for standard type AFX fans is Airflow A in
accordance with the diagram. The fans may be mounted horizontally or
vertically in accordance with the figures of construction.
Top

|